InstructionsRead and retain carefully for as long as the product is being used. It contains vital information on the operation and installation of you
- In a bedsit, the CO alarm should be placed as far away from the cooking appliance as possible, but near to where the person sleeps- If the appliance
(13) In a bathroom or other areas where the CO alarm may be exposed to water splashes, dripping or condensation (e.g. above an electric kettl
12300mm150mm1 to 3 m1 to 3 mDEAD AIRDON'T LOCATEHERECO AlarmFigure 1Location in room with a fuel burning appliance
13CO Alarmabout1 to 2mFigure 3Location in bedrooms & other rooms remote from the appliance(i.e. at breathing level)300mmCO AlarmFigure 2Location i
4. InstallationWarning: The Installations of this apparatus should not be used for a subsitute for proper installation, use and maint
7. Carefully line up the Alarm on the base, gentle press home & twist on – see figure 4. (This connects the batteries). The red, ambe
If necessary it is possible to further secure or tamperproof the Alarm by using a No.2 or No.4 (2 to 3mm diameter - not supplied) self tapping screw 6
MonitoringThe Ei207 / 208 series CO alarm will self check (monitor) itself and give a status update every minute (approx) if there are any problems.Th
Use the narrow nozzle of a vacuum cleaner to remove fluff and other contamination from the cover slots and gas entry holes.Caution: Do not paint the C
(For Ei208 Models Only) These alarms uses powered for life lithium batteries and are not replaceable. Check the ‘Replace by’ label on the side wall -
ModelEi2072xAAA Replaceable BatteriesModel ChartLong Life Battery Built-inEi207DNoNoRFCapabilityNoNoRF ModuleSuppliedNoYesLCDDisplayModelEi208WEi208WR
the Alarm into the smoke filled bag and seal it closed. Within seconds, the red light will begin to flash (as per Table B) to confirm that the Alarm h
Note: When ventilation is provided by leaving the window and doors open, the CO build up may have dissipated by the time help arrives and th
(3) These appliances must “breathe in” air to burn the fuel properly. Know where the air comes from and ensure vents/air bricks etc. remain unobs
8. Technical SpecificationPower : Two Alkaline AAA type batteries (replaceable) – Ei207 models Powered for life lithium battery (non-replaceable)
9. Getting the CO Alarm ServicedIf your CO Alarm fails to work after you have carefully read all the instructions, checked the unit has
11. Limitations of CO Alarms(1) The CO Alarm will not work without good batteries. If the batteries have been drained the Alarm will not
(5) CO Alarms are not a substitute for life insurance. House-holders are responsible for their own insurance. The CO Alarm warns of increasing
12. TroubleshootingALARM DOES NOT WORK WITH THE TEST BUTTON:(1) Check the Alarm is secured correctly on the mounting plate.(2) Wait 15 seconds after c
(6) If the Alarm is fitted with an RF Module, ensure that there are no problems with the other RF interconnected Alarms and that all Alarms are housec
13. Display & Indicator Summary29
32. Location & Positioning1. Read This First ...2. Ca
30Power Up1 flash1 flashOnOnOnOnOn1 flashOffOffOffOffOff1 Flash (every sec)Flashing (as per table B)Button Test (Weekly)Unit Sensing CO gas itselfSens
31The crossed out wheelie bin symbol that is on your product indicates that this product should not be disposed of via the normal househo
14. Contact UsAico Ltd. Mile End Business Park, Maesbury Rd, Oswestry,Shropshire SY10 8NN, U.K.Tel: 0870 758 4000 www.aico.co.ukEi Electronics. Shanno
1. Read This First• Congratulations on becoming the owner of an Ei Carbon Monoxide Alarm. This will help protect you and your househ
2. Carbon Monoxide – The Silent Killer2.1 What is Carbon Monoxide ?Many people are killed each year, and many more suffer ill health from
2.3 Symptoms of Carbon Monoxide PoisoningTable A 35 The maximum allowable concentration for continuous exposure in any 8 hour period accordi
7Red Light Display IconSounder(before horn sounds)(Pre Alarm) (Alarm)Display Icon(after horn sounds)CO Gas Level0 < ppm < 10 ppm* unless it has
8Pre-Alarm: When the Alarm detects over 43 ppm CO the red light flashes in accordance with Table B. This helps locate CO leaks as the unit gives an in
Reset Memory: Hold down the test button until the red light stops and the green light starts flashing. Cover the horn with a cloth to muf